Sprinklers · Upright sprinkler
Intermediate-level upright sprinkler
- K-factorK-factorThe sprinkler's discharge coefficient: flow = K × √pressure. A higher K gives more water at the same pressure. K5.6 (K80 metric) is the usual head for light and ordinary hazard.
- K8.0 (K115 metric)
- ResponseResponseHow fast the heat-sensitive element reacts. Quick response heads open sooner and are usual in light hazard areas such as hotels, offices and hospitals; standard response suits many ordinary hazard and storage areas.
- Quick
- ThreadThreadNPT is the American taper thread; BSPT (ISO 7-1) is the British taper thread. Match the thread to the fittings used on the project.
- ¾" NPT (20 mm)
- Application
- In-rack storage, ordinary hazard
- TemperatureTemperature ratingThe temperature at which the glass bulb or link breaks and the sprinkler opens. 68 °C (red bulb) suits normal ceilings; hot spaces such as kitchens and plant rooms need a higher rating.
- 57–141 °C
- Finish
- Plain brass and others
- Range
- K8.0 (metric K115), ¾" NPT (20 mm), quick response, Intermediate level (in-rack storage), ordinary hazardTemps: 135°F/57°C, 155°F/68°C, 175°F/79°C, 200°F/93°C, 286°F/141°CFinishes: Plain brassMax pressure: See data sheet, data sheet 40.23
The model and its listing reference are in your offer, so you can check the listing yourself (how to check a listing). Listings belong to the manufacturer.
Other products in Upright sprinkler · 8 of 12
Upright sprinkler
Upright sprinkler
Upright sprinkler
Upright sprinkler
Upright sprinkler
Upright sprinkler
Upright sprinkler
Upright sprinkler
No product here fits every option you set. Your line keeps your options and our engineer offers the closest match.
Have a BOQ or a set of drawings?
Send it today. We reply with a priced offer and our comments on the design, usually within two working days.